5925-01-583-6550
Circuit Breaker
1 parts / 1 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| APGN-66-28039-1 | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 2 | 2 |
Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M
CAGE 81349DEMIL
A
HMIC
P
PMIC
A
ESD/EMI
A
| MRC | Requirement | Reply |
|---|---|---|
| AAJE | THREAD PITCH DIAMETERS | +0.4752 TO 0.4787 INCHES |
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ABXD | BUSHING LENGTH | 0.625 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 2.000 INCHES NOMINAL |
| ADAT | BODY WIDTH | 2.250 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.232 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING WITH PANEL SEAL |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRK | AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 115.0 AC NOMINAL FIRST LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.500 INCHES |
| CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS FIRST LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 3.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT AND SALT SPRAY PROOF AND MOISTURE RESISTANT |
| FEAT | SPECIAL FEATURES | RELAY COIL AT POLE ONE IS INSTANEOUS TRIP |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UN |
| TTQY | TERMINAL TYPE AND QUANTITY | 8 TAB W/SCREW |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-583-6550
NSN 5925-01-583-6550 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 1 part number associated with this NSN from 1 manufacturer.
To find the part number for NSN 5925-01-583-6550, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.