5925-01-264-5080
Circuit Breaker
3 parts / 3 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| JA3S-T38-DB-04-W-4.0A/415V/2 | 74193 | Eaton Corp Heinemann Products Commercial Controls Div | 3 | 9 |
| 42141-345-00-1 | K4556 | British Aerospace Defence Systems Ltd T/a Bae Systems | 5 | 9 |
| 42141-345-00-1 | KC1M9 | Bae Systems Maritime Services Limited | 5 | 2 |
Eaton Corp Heinemann Products Commercial Controls Div
CAGE 74193British Aerospace Defence Systems Ltd T/a Bae Systems
CAGE K4556Bae Systems Maritime Services Limited
CAGE KC1M9DEMIL
A
HMIC
P
PMIC
U
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 2.245 INCHES MINIMUM AND 2.255 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.835 INCHES MINIMUM AND 1.845 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 4.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 415.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-264-5080
NSN 5925-01-264-5080 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 3 part numbers associated with this NSN from 3 manufacturers.