5925-01-237-6865
Circuit Breaker
3 parts / 1 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| M39019/5-230 | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 2 | 2 |
| M39019-5-49 | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 5 | 9 |
| MIL-C-39019/5 | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 4 | 1 |
Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M
CAGE 81349DEMIL
A
HMIC
P
PMIC
A
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ABXD | BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
| ADAQ | BODY LENGTH | 1.937 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 1.562 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 50.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC AND 500.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.950 MAXIMUM ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS |
| FREQ | FREQUENCY IN HERTZ | 60.0 OR 400.0 ALL LOCATIONS |
| TEST | TEST DATA DOCUMENT | 81349-MIL-C-39019 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
| ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-81349/5 GOVERNMENT SPECIFICATION |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-237-6865
NSN 5925-01-237-6865 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 3 part numbers associated with this NSN from 1 manufacturer.
To find the part number for NSN 5925-01-237-6865, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.