5925-01-200-7812
Circuit Breaker
Unit Price
$259.74
per EA
2 parts / 2 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| 5050213-2 | 57958 | Signals Warfare Project Manager | 3 | 9 |
| CD4-Z132-2 | 74193 | Eaton Corp Heinemann Products Commercial Controls Div | 5 | 9 |
Signals Warfare Project Manager
CAGE 57958Eaton Corp Heinemann Products Commercial Controls Div
CAGE 74193| Effective Date | Unit Price | UI | SLC |
|---|---|---|---|
| 01-OCT-2025 | $259.74 | EA | 0 |
DEMIL
A
HMIC
P
PMIC
A
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| ABTD | MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 3.544 INCHES NOMINAL |
| ADAT | BODY WIDTH | 4.128 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.546 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.032 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.032 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.218 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.609 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 4 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE(S) AND 8 SLOT |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 0.0 AMPERES AC FOURTH LOCATION |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC FIRST LOCATION |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC THIRD LOCATION |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC SECOND LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FIRST LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC FOURTH LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC THIRD LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SHUNT TRIP FOURTH LOCATION |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT THIRD LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.530 MINIMUM AT 200 PCT AND 1.500 MAXIMUM AT 200 PCT FOURTH LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 105.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 9 THREADED STUD |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-200-7812
NSN 5925-01-200-7812 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 2 part numbers associated with this NSN from 2 manufacturers.
The current government unit price for NSN 5925-01-200-7812 is $259.74.
To find the part number for NSN 5925-01-200-7812, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.