NSN

5925-01-174-6558

Circuit Breaker

FSC 5925CIRCUIT BREAKERSFSG 59ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS

2 parts / 2 mfrs

Part Numbers for NSN 5925-01-174-65582 records
Part NumberCAGEManufacturerRNCCRNVC
CD2-B2B3-40-125-174193Eaton Corp Heinemann Products Commercial Controls Div39
3522 500 26801H0203Thales Nederland52
Manufacturers (2)

Eaton Corp Heinemann Products Commercial Controls Div

CAGE 74193
View NSNs

Thales Nederland

CAGE H0203
View NSNs
Identification Data

DEMIL

A

HMIC

P

PMIC

U

ESD/EMI

Item Characteristics
MRCRequirementReply
AAQLBODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
ABTDMOUNTING SLOT WIDTH0.178 INCHES NOMINAL
ADAQBODY LENGTH5.769 INCHES MINIMUM AND 5.831 INCHES MAXIMUM
ADATBODY WIDTH2.041 INCHES MINIMUM AND 2.103 INCHES MAXIMUM
ADAUBODY HEIGHT2.609 INCHES NOMINAL
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.516 INCHES MINIMUM AND 3.578 INCHES MAXIMUM
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.995 INCHES MINIMUM AND 1.057 INCHES MAXIMUM
AEBVUNTHREADED MOUNTING HOLE DIAMETER0.164 INCHES NOMINAL
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.719 INCHES MINIMUM AND 2.781 INCHES MAXIMUM
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.995 INCHES MINIMUM AND 1.057 INCHES MAXIMUM
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHT0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCE3.172 INCHES MINIMUM AND 3.296 INCHES MAXIMUM
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE(S) AND 2 UNTHREADED HOLE(S) AND 2 SLOT
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES DC ALL LOCATIONS
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 DC ALL LOCATIONS
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 DC ALL LOCATIONS
CPRHCIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CPRJTRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
CPRLTRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
CPRPULTIMATE TRIP TIME PER POLE IN SECONDS1000.000 MAXIMUM ALL LOCATIONS
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
CQJXNOMINAL THREAD SIZE0.138 INCHES
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT15.000 MINIMUM AT 200 PCT AND 40.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CSSXSWITCH CURRENT RATING AND TYPE IN AMPS3.0 DC
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTS30.0 DC
MATTMATERIALPLASTIC CASE
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITY4 THREADED STUD

Need full procurement data, packaging, and standardization info?

View Complete NSN Data on NSN Lookup

Quick Reference

NSN5925-01-174-6558
NIIN011746558
FSC5925
DEMILA
PARTS2
MFRS2

About NSN 5925-01-174-6558

NSN 5925-01-174-6558 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 2 part numbers associated with this NSN from 2 manufacturers.

To find the part number for NSN 5925-01-174-6558, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.