5925-01-078-2374
Circuit Breaker
3 parts / 3 mfrs
Lucent Technologies Inc Advanced Technology Systems
CAGE 01714L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.
CAGE 30086Siemens Energy and Automation Inc Ite Circuit Protection Div
CAGE 66842DEMIL
A
HMIC
P
PMIC
S
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 5.984 INCHES MINIMUM AND 6.016 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 4.484 INCHES MINIMUM AND 4.516 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.109 INCHES MINIMUM AND 5.141 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.577 INCHES MINIMUM AND 4.609 INCHES MAXIMUM |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.202 INCHES MINIMUM AND 0.234 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.983 INCHES MINIMUM AND 4.015 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
| CQJX | NOMINAL THREAD SIZE | 0.164 INCHES |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT EACH POLE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
| CRTK | SWITCH TERMINAL TYPE | WIRE LEAD |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| PMLC | PRECIOUS MATERIAL AND LOCATION | TERMINAL AND C0NTACT SURFACES SILVER |
| PRMT | PRECIOUS MATERIAL | SILVER |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |
| ZZZK | SPECIFICATION/STANDARD DATA | 01714-G376972-1 MANUFACTURERS SOURCE CONTROL |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-078-2374
NSN 5925-01-078-2374 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 3 part numbers associated with this NSN from 3 manufacturers.
To find the part number for NSN 5925-01-078-2374, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.