NSN

5925-01-073-9228

Circuit Breaker

FSC 5925CIRCUIT BREAKERSFSG 59ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS

2 parts / 1 mfrs

Part Numbers for NSN 5925-01-073-92282 records
Part NumberCAGEManufacturerRNCCRNVC
WC375/07-00281348Federal Specifications Promulgated By General Services Administration Washington Dc22
W-C-375/781348Federal Specifications Promulgated By General Services Administration Washington Dc41
Manufacturers (1)

Federal Specifications Promulgated By General Services Administration Washington Dc

CAGE 81348
View NSNs
Identification Data

DEMIL

A

HMIC

P

PMIC

A

ESD/EMI

Item Characteristics
MRCRequirementReply
AAQLBODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
ADAQBODY LENGTH3.025 INCHES MINIMUM AND 3.065 INCHES MAXIMUM
ADATBODY WIDTH2.193 INCHES MINIMUM AND 2.241 INCHES MAXIMUM
ADAUBODY HEIGHT2.371 INCHES MINIMUM AND 2.433 INCHES MAXIMUM
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES NOMINAL
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHT0.188 INCHES NOMINAL
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITY6 TERMINAL
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC ALL LOCATIONS
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
CPRHCIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CPRJTRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
CPRLTRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 ALL LOCATIONS
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDCORROSION RESISTANT
CRCFTRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
FREQFREQUENCY IN HERTZ60.0 ALL LOCATIONS
MATTMATERIALPLASTIC CASE
TESTTEST DATA DOCUMENT81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
TTQYTERMINAL TYPE AND QUANTITY3 CLIP AND 3 COMPRESSION
ZZZKSPECIFICATION/STANDARD DATA81348-W-C-375/7 GOVERNMENT SPECIFICATION

Need full procurement data, packaging, and standardization info?

View Complete NSN Data on NSN Lookup

Quick Reference

NSN5925-01-073-9228
NIIN010739228
FSC5925
DEMILA
PARTS2
MFRS1

About NSN 5925-01-073-9228

NSN 5925-01-073-9228 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 2 part numbers associated with this NSN from 1 manufacturer.

To find the part number for NSN 5925-01-073-9228, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.