5925-01-024-3807
Circuit Breaker
2 parts / 2 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| CP35-5-70-2J7P | 25500 | Lockheed Martin Corporation Dba Lockheed Martin Div Rotary and Mission Systems | 7 | 2 |
| AM12HK2-120VACCURVE16 | 74193 | Eaton Corp Heinemann Products Commercial Controls Div | 3 | 9 |
Lockheed Martin Corporation Dba Lockheed Martin Div Rotary and Mission Systems
CAGE 25500Eaton Corp Heinemann Products Commercial Controls Div
CAGE 74193DEMIL
A
HMIC
P
PMIC
U
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 2.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.200 MINIMUM AT 200 PCT AND 0.650 MAXIMUM AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 2.5 AC AND 1.0 DC |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
| CTJS | UNPACKAGED UNIT WEIGHT | 4.250 OUNCES NOMINAL |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| MATT | MATERIAL | PLASTIC CASE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-01-024-3807
NSN 5925-01-024-3807 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 2 part numbers associated with this NSN from 2 manufacturers.