5925-00-876-9219
Circuit Breaker
5 parts / 4 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| S458D509G14 | 11660 | Westinghouse Electric Corp Control Business Unit | 5 | 9 |
| ETN2753 | 30086 | L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc. | 5 | 2 |
| S458D509G14 | 79500 | Westinghouse Electric Corp | 5 | 2 |
| 458D509G14 | 89946 | Eaton Corporation Dba Eaton Inoac | 5 | 2 |
| S458D509G14 | 89946 | Eaton Corporation Dba Eaton Inoac | 3 | 2 |
Westinghouse Electric Corp Control Business Unit
CAGE 11660L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.
CAGE 30086Westinghouse Electric Corp
CAGE 79500Eaton Corporation Dba Eaton Inoac
CAGE 89946DEMIL
A
HMIC
P
PMIC
U
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 6.500 INCHES NOMINAL |
| ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 3.875 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.938 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.312 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.656 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.188 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 AMPERES AC AND 75.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 250.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 15000.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
About NSN 5925-00-876-9219
NSN 5925-00-876-9219 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 5 part numbers associated with this NSN from 4 manufacturers.
To find the part number for NSN 5925-00-876-9219, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.