5925-00-643-7549
Circuit Breaker
Unit Price
$325.15
per EA
4 parts / 3 mfrs
| Part Number | CAGE | Manufacturer | RNCC | RNVC |
|---|---|---|---|---|
| DMS 79009B | 16236 | Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (Vendor Item Drawings) | 5 | 9 |
| TN231200 | 71669 | General Electric Co Switchgear and Control Division of Apparatus Group | C | 1 |
| ALB-10/200A | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 2 | 2 |
| MIL-C-17588 | 81349 | Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M | 4 | 1 |
Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (Vendor Item Drawings)
CAGE 16236General Electric Co Switchgear and Control Division of Apparatus Group
CAGE 71669Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M
CAGE 81349| Effective Date | Unit Price | UI | SLC |
|---|---|---|---|
| 01-OCT-2025 | $325.15 | EA | 0 |
| 01-OCT-2025 | $325.15 | EA | 0 |
DEMIL
A
HMIC
P
PMIC
U
ESD/EMI
| MRC | Requirement | Reply |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 5.000 INCHES NOMINAL |
| ADAT | BODY WIDTH | 4.750 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.625 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.688 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.250 INCHES NOMINAL |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, SINGLE THROW, NORMALLY CLOSED |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.312 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.625 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE(S) |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 20 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC AND 200.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC AND 125.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 3600.000 NOMINAL ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
| CQJX | NOMINAL THREAD SIZE | 0.250 INCHES |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
| CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 10.0 DC |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 125.0 DC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MATT | MATERIAL | PLASTIC CASE |
| TEST | TEST DATA DOCUMENT | 81349-MIL-C-17588 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
| ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-17588 GOVERNMENT SPECIFICATION |
Need full procurement data, packaging, and standardization info?
View Complete NSN Data on NSN LookupQuick Reference
Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (Vendor Item Drawings)
CAGE 16236
General Electric Co Switchgear and Control Division of Apparatus Group
CAGE 71669
Military Specifications Promulgated By Military Departments/Agencies Under Authority of Defense Standardization Manual 4120 3-M
CAGE 81349
About NSN 5925-00-643-7549
NSN 5925-00-643-7549 is a National Stock Number assigned to Circuit Breaker. This NSN part number belongs to Federal Supply Class 5925 (CIRCUIT BREAKERS) under Federal Supply Group 59 (ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS). There are 4 part numbers associated with this NSN from 3 manufacturers.
The current government unit price for NSN 5925-00-643-7549 is $325.15. Price history shows 2 recorded price changes.
To find the part number for NSN 5925-00-643-7549, refer to the part number cross-reference table above. Each part number is linked to its manufacturer through a CAGE (Commercial and Government Entity) code.